Optical smoke detector ES Detect

Cod. 800371
  1. Home
  2. Fire Detection Technology
  3. Optical smoke detector ES Detect

Optical smoke detector ES Detect

Optical smoke detector ES Detect for reliable detection of fires. Continuous monitoring of the state of the optical chamber and sensor electronics, including continuous control of CPU functionality. Automatic compensation of drift in case of variations due to critical environmental conditions (e.g. dust and / or humidity). Presence of experimental algorithms of false alarms which, when suitably compared with the environmental information collected, save them from being eliminated and not evaluated as fire alarms. Using further specific algorithms, the detector is able to identify any electromagnetic interferences generated by devices such as inverters, conveyor belts, radio / wireless devices and audio speakers. Two-color LED for alarm status evaluation and simplified maintenance.

A remote indicator can also be connected.

Accessories:
767800 Assembly bracket
805590 Standard IQ8Quad detector base
805591 Detector base with IQ8Quad relay contact

Features:

• Optimally matched to the ES Line system
• With multisensor detectors for the detection of all fires, even under the most difficult operating conditions
• Up to 30 detectors per detection group
• Uniform response sensitivity of the detector for all different types of fire for the multisensor detectors
• Large distance between signal and interference magnitudes due to special sensor and electronics design for suppressing electromagnetic influences
• Automatic adaptation to varying environmental influences
• Electronic compensation also called driftcompensation of long-term influences of contamination or aging
• High reliability against false alarms by temporal evaluation of different sensor criteria, with built-in insect screen and sealed against rear air flow entry
• Exclusion of signal forms not typical of fires through special filter algorithms
• Automatic self-monitoring of the detector electronics
• Automatic self-monitoring of sensors for function and condition
• Designation of the heat detector by a black ring on the light pipe
• Hours of operation, alarm and fault counter in each detector
• Operation data retrieval of all detectors of a group with standard service PC and field bus interface
• Detector LED for alarm display and as an identification display in the service (for maintenance with 8000 tools)
• Standard socket and relay base
• Socket adapter for ceiling installation
• Dust caps optional for fire detectors and detector base
• Kit for suspended mounting

Common technical data

Operating voltage
8 ... 42 V DC
Quiescent current @ 9 V DC
30 μA
Alarm current @ 9 V DC
9 mA
Area to be monitored
110 m²
Height to be monitored
12 m
Air velocity
0 m/s ... 25,4 m/s
Application temperature
-20 °C ... 72 °C
Storage temperature
-25 °C ... 75 °C
Air humidity
< 95 %
Type of protection
IP 40 with base, up to IP 43 with base and option
Material
ABS
Color
white, similar to RAL 9010
Weight
approx. 110 g
Detector specification
EN 54-7
Dimensions
Ø: 117 mm H: 49 mm (62 mm incl. detector base)
NOTE
Special colors on request! For the maintenance of the ES Detect detectors, the programming software tools 8000 from version V1.24 in combination with the red EOL-I (part number 808626) is required. In order to pass through existing wires, the WAGO grips (e.g., type 243-204 (Ø 0.5-1 mm) or 273/104 (0.75-2.5 mm²), can be integrated into the detector base.
Shipping
Without detector base

Do not hesitate to contact us

Fill in the form below and we will get back to you as soon as possible!