ES line is a compact, powerful and professional conventional fire control panel to monitor small environments. It supports up to 8 conventional zones and up to 30 detectors per zone. It has an integrated display to view the status of each zone. The easy and intuitive interface and self-explanatory indications allow for ease of use and quick start-up, even without the use of computers. The ES Line also offers high flexibility in defining cause/effect functions and control functions. The integrated interface allows you to connect the RS485 of the fire brigade (FB, FAT). ES Line is certified according to EN 54-2, EN 54-4 and VdS standards.

Ideal for small facilities such as schools, law firms, service companies, restaurants, craft businesses, doctors’ offices, pharmacies or retail outlets.

In accordance with the EN 54 standard, the EOL-I end-of-line device (product code 808626, optional) and the EOL-O device (product code 808624, optional) are required for the optical device lines to monitor the detection lines. – acoustics.

Features:

• 8 sensor groups with up to 30 sensors in each sensor group (conventional panel supports up to 240 conventional devices in total)
• Large LCD display with 8 rows x 40 characters
• Integrated sensor group single display
• Optimized commissioning, maintenance and operation
• Simple configuration and programming on the keypad
• Four relays, freely programmable, non-monitored, potential free, max. 30 V DC / 2 A or 60 V DC / 1 A
• 2 outputs for connecting acoustic or optical sounders according to EN 54-13 (29 V DC/ max.
500 mA)
• 1 interface to a transmission unit for fire alarm routing equipment (FARE) (12 V DC / max. 200 mA)
• 1 interface to a transmission unit for fault warnings (12 V DC / max. 200 mA)
• 1 standard interface extinguisher for fire control system type C according to DIN EN 54-2
• RS485 for connecting to fire brigade operating panel and fire brigade display panel
• 1 output UBext 29 V / 0.5A, for power supply of external bus users
• 72 h emergency current bridge
• “Delay of relaying” function (PM operating mode according to DIN VDE 0833-2 for preventing false
alarms, delay / verify)
• “2-detection dependency” function (TM operating mode according to DIN VDE 0833-2 for preventing false alarms), alternatively programmable as intermediate alarm storage or 2-zone dependency between the detector zones
• Operating panel with alphanumerical display
• Large LCD display with 8 rows x 40 characters
• Alarm counter for up to 10,000 trips
• Event memory for up to 10,000 events

Technical specifications:

Rated voltage
230 V AC
Rated frequency
50 Hz ... 60 Hz
Rated current
0,84 A
Output voltage
29 V DC
Quiescent current
approx. 100 mA
Battery capacity
max. 2 x 12 Ah
Ambient temperature
-5 °C ... 45 °C
Storage temperature
-5 °C ... 50 °C
Air humidity
< 95 %
Type of protection
IP 30
Housing
ABS, 10 % glass fiber reinforced, V-0
Color
gray, similar to Pantone 538
Weight
approx. 5 kg (without batteries)
Dimensions
W: 450 mm H: 320 mm D: 185 mm
Declaration of Performance
DoP-21233141217
NOTE
Detector Series ES Detect and conventional devices are compatible with this FACP.Due to its nature, this article contains components classified as dangerous goods. Please clarify in advance with your forwarding agent if he accepts the transport of dangerous goods and if necessary observe the import regulations. The dangerous goods class for road transport or air transport is as follows: UN-No. UN3090 ADR-Class 9